Please use this identifier to cite or link to this item: https://repositori.uma.ac.id/handle/123456789/18378
Full metadata record
DC FieldValueLanguage
dc.contributor.authorDaut, I-
dc.contributor.authorMaizana, Dina-
dc.contributor.authorTaib, S-
dc.date.accessioned2022-11-16T06:09:14Z-
dc.date.available2022-11-16T06:09:14Z-
dc.date.issued2008-04-
dc.identifier.issnISBN CD:978-0-88986-732-1-
dc.identifier.urihttps://repositori.uma.ac.id/handle/123456789/18378-
dc.description10 Pagesen_US
dc.description.abstractThis paper describes the result of measurement of flux distribution on 100KVA 3phase distribution transformer assembled with 45 T-joint and mitred lap CORNER joint with stagger yoke. The measurement involves the variation of flux The flux distributions have been measured using no load test by arrays of search coil in M5 (CGO) grades material of transformer core laminations. The localised flux density at the outer 45 T-joint is 90 mT and rises to be 148 mT at the inner 45 T-joint and the localised flux density at the outer corner-joint is 103 mT and rises to be 198 mT at the inner comer-joint when the transformer core energized 1 T 50H2 A small amount of flux deviation from the rolling direction occurs at the overlap.en_US
dc.language.isoenen_US
dc.publisherIASTED International Conference Power and Energy Systems (AsiaPES 2008)en_US
dc.relation.ispartofseriesAsiaPES 2008;Proceedings of the Fourth-
dc.subjectflux distributionen_US
dc.subjecttransformer coreen_US
dc.subjectsearch coilen_US
dc.titleMeasurement of Flux Distribution on 100kVA 3Phase Distribution Transformer Assembled With 45 T-Joint and Mitred Lap Corner Joint with Stagger Yoke by Using Search Coilen_US
dc.typeArticleen_US
Appears in Collections:Published Articles



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.